VisualPhase
Chapter: Overview · Description · Device configurations“Complete service package”
With the VisualPhase line you get a type series of handy, exact and easily operated multi-functional devices with integrated voltage detectors, phase comparator and maintenance testers.
Equipped with a thorough self test to ensure reliable function, a permanently enabled interface-tester to warn against defect interfaces and the connectability to HR, MR, LR, LRM or LRP string parts every VisualPhase delivers uncompromising safety.
Moreover the standardized maintenance test can be carried out due to the integrated ammeter as well as the rate of operating / nominal voltage of the specific switchgear can be adjusted on-site.
The integrated “Universal Phase Comparator” can compare two different interface signals, even if they are of different interface types or voltages. A unique error control avoids switching errors caused by erratic or unfeasible phase comparison. The digital phase display enables a phase sequence indicator or to sync different net segments.
Application and technique
VisualPhase is a dual phase VDS (Voltage Detecting System) with integrated UPC (Universal Phase Comparator) according to IEC/EN 61243-5 (DIN VDE 0682 T415). LR is the primary fitting system. Respective adapters for HR, MR, LRM and LRP string parts are available.
The evaluated indication of the interface current is carried out by means of two bright LEDs per phase, which display the conditions voltage absent, residual voltage, voltage present, string part Ok and high current respectively. Additionally you can read the digital ammeter to get the live interface current in [I/µA].
The multi-functional display can show by preference the phase difference φ (-180 ... +180°) or the input frequency.
The evaluation of the actual voltage state is accomplished with an rms-value measuring method independent of the applied waveform. Fast zero-crossing detectors with digital offset compensation carry out phase comparison.
By means of the active display no external light source is required for metering, like it is needed for passive LC-displays: you rather deplete torch light batteries than device-batteries.
The integrated self-test ensures unfailing operation. It starts automatically whenever the device is switched on. After pushing the button once the device checks the connection leads, the LEDs, the battery voltage and the correct functioning of electronic measuring circuits and software. When an error is detected you will be notified of fault condition by deterministic flashlight signals and afterwards the device shuts down.
Long-lasting lithium batteries power the thrifty microcontroller electronics for many operating hours.
Device configurations
Order-no. | Name |
---|---|
VPb-01 | VisualPhase basic - basic unit |
VPb-01/K | VisualPhase basic (Set) |
VPL-01 | VisualPhase LCD - basic unit |
VPL-01/K | VisualPhase LCD (Set) |